        1. PRODUCT CENTER
          IP6000d

          IP6000 series flameproof positioner is mounted on pneumatic actuators. It's used to control air intake and exhaust of the pneumatic actuators to drive the valve position to the set point by calculating both data from 4-20mA DC signal and feedback position.

          • Easy to install, one-key auto-tune calibration
          • Mature and reliable piezo module, imported from Germany
          • Numerous functions can be activated(e.g. characteristic curves and limits)
          Technical specification
          Technical data
          Mechanical Dimensions
          Structure
          Electrical connections
          Pneumatic connections
          Wiring diagram
          Principle block diagram
          Mounting components
          Combination mode
          • Installation type
            Acting type
            Explosion proof
            Feedback signal
            HART
            Mounting kit & lever
            Pressure gauge
            Power off state
            Min. ambient temp

            Normal linear(L

            Remote linear*(FL

            Normal rotary(R

            Remote rotary*(FR

            Separate*(S

            Single acting(S

            Double acting(D

            Non explosion(n

            Ex ia IIC T4/T6 Ga(i

            Ex d IIC T6 Gb(d

            No(0

            Yes(1

            No(0

            Yes(1

            No(0

            Linear(1

            Rotary(2

            No(0

            Yes(1

            Safe(S

            Freeze(F

            -20℃(N

            -40℃(L

          In the installation type options, the options marked with * (FL, FR and S) do NOT support explosion proof option d (Ex d IIC T6 Gb).
          * marked option S (separate type) does NOT support the Min. ambient temperature option L (-40℃).

          Technical Data

          Enclosure material

          Aluminum
          Pressure gauge block material

          Aluminum, anodized

          Input signal

          Input resistance: 120Ω   

          Limit voltage: 28V

          Output signal

          Feedback type: 2-wire 4~20mA signal, internal resistance 120Ω

          Digital communication protocol HART 7
          Minimum operating current 3.8mA
          Steady state air consumption ≤ 0.4 L/min
          Stroke range

          Default linear type: 10~100mm

          Default rotary type: 30~100°

          Optional mounting bracket: Hard connection or soft connection

          Pneumatic data

          Air quality meets ISO 8573-1 standard

          Pressure range:1.4~7bar(20.3~101.5psi)

          Solid particle size and density: Grade 3

          Pressure dew point: Class 3 (minimum 20K (36°F) lower than the ambient temperature)

          Oil content: Class 3

          Vibration resistance

          0.15mm, 10Hz-60Hz, 20 cycle/axis 

          20m/s2, 60Hz-500Hz, 20 cycle/axis Recommended range for control valve ≤20m/s2, no resonance peak

          Electrical connection M20×1.5
          Pneumatical connection G1/4
          Protection class IP66

          Basic error & Hysteresis error

          ≤ 1%
          Ambient temperature

          Default type:-20°C ~ +60 ℃

          Low temperature type:-40°C ~ +60 ℃

          Explosion-proof grade and applicable zone

          Ex d IIC T6 Gb apply to Zone 1,Zone 2



          Connection

          Description
          IN+

          4-20 mA input signal +

          IN-

          4-20 mA input signal -

          OUT+

          Feedback signal module 18-30 V DC+

          OUT-

          Feedback signal module 4-20 mA output

          Connection Description

          SUP

          Air supply input

          OUT1

          Pilot air outlet 1

          OUT2    

          Pilot air outlet 2


          • Ex d linear type
          • Ex d rotary type
          亚洲av日韩av欧v在线天堂,裸体美女洗澡视频网站,亚洲中文字幕 在线观看,午夜精品视频最新 <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <文本链> <文本链> <文本链> <文本链> <文本链> <文本链>